ULTROL CPA Control Panels - Airline Series
Applications
ULTROL Airline Series Control Panels (CPA) are designed and built to the high-technological standards required by today's engineers for precise airflow and environmental pressure control.
Several standard models are available for the measurement, indication, and control of duct static pressure, variable volume supply-and-return fan synchronization, laboratory or clean room static pressure and flow, as well as, manual control and alarm systems.
The panels are normally supplied as components in a complete airflow measuring and control system which includes flow and pressure sensors. See ULTRAC Specifications.
Description
ULTROL Airline Panels are constructed to industrial process plant standards to provide long-term, trouble-free operation with minimum maintenance. Equipment is installed in NEMA 1 enclosures with removable, internal instrument-mounting panels.
Sizes vary from 12" x 16" to 36" x 48" as required.
Standard specifications describe the equipment most often furnished. Panels will vary according to specifications for a particular system.
Airline Series Panels may be combined to economically meet a project specification.
Standard Specifications
ENCLOSURE: NEMA 1 with removable inner mounting panel. 14-gauge steel EXTERNAL FINISH: Primed, painted light gray INTERNAL FINISH: Primed INNER PANEL FINISH: Primed, white enamel topcoat INTERNAL INTERCONNECTION FITTINGS: Brass, barb-type INTERNAL TUBING: 1/4" o.d. polyethylene and 1/8" o.d. tygon FIELD MOUNTING PROVISIONS: Slotted holes in enclosure back RG-AIR SUPPLY: 250 psig internal regulator, 5-micron filter & oil sensor PROCESS CONNECTING FITTINGS: Brass bulkhead with 1/4" female coupling IDENTIFICATION NAMEPLATES: Laminated plastic, 1" x 3" with black & white letters G1-DRY-TYPE INDICATING GAUGES: Flow, static pressure and filter indications; Dwyer Magnehelic G2-PROCESS INDICATING GAUGES: 3 1/2" 3-15 psig receiver G3-SETPOINT INDICATING GAUGES: 3 1/2" 3-15 psig receiver G4-CONTROLLER OUTPUT GAUGES: 2 1/2" 0-30 psig G5-AIR SUPPLY PRESSURE GAUGES: 2 1/2" 0-30 psig PROCESS SETPOINT ADJUSTMENT METHOD: Variable air pressure regulator
Available Options
AL - Alarm sensing switches, electric
AT - Alarm light, audible device, acknowledge button, electric
AP - Alarm, pneumatic visual indicator, two states
KL - Key locking front panel
G6 - Custom gauge, 3 1/2" dial, 3-15 psig receiver
G7 - Custom gauge, 4 1/2" dial, 3-15 psig receiver
G8 - Custom gauge, 6" dial, 3-15 psig receiver
G9 - Dry-type indicating gauge, filter maintenance
NP - Night cycle, pneumatic remote control provision, 20 psig 115 VAC
SS - Summing of multiple signals
SP - Remote setpoint regulator w/indicating gauge
FR - Fire resistant internal tubing
SL - Selector switch for selection of control point
PI - Pneumatic transducer, for electronic output signal
IP - Current to pneumatic transducer, for electric input signal
IR - Indicating recorder
FP - Fan operating switching valve, 0-20 psig pneumatic
FE - Fan operating switching valve, 115 VAC electric
OP - Overpressure protection, purging transmitters
ZZ - Special provision (identify requirements)
|